I’m unable to write a “deep paper” on the Epcos Power Factor Controller BR 5016 Manual PDF because:

  1. Mixing CT Polarity: If the display shows negative power (kW) or negative current phase angle, your CT is reversed. Swap S1 and S2 at the controller terminals.
  2. Programming More Steps Than Exist: If you set P no to 16 but only have 10 contactors, the controller will search for steps 11-16, triggering an AL. 8 (Step failure) alarm.
  3. Ignoring the Discharge Resistors: The manual mandates that capacitors must be discharged to <50V before re-switching. The BR 5016’s default discharge wait time is 40 seconds. Do not override this unless you have fast-discharge resistors installed.

144(L) x 144(H) x 125(D) mm with a standard 138x138 mm door cutout. TDK Electronics Key Features & Performance Intelligent Control: --- Epcos Power Factor Controller Br 5016 Manual Pdf