is a digital temperature controller often used in industrial machinery like plastic molding machines, ovens, and packaging equipment. It typically features an LED display for both the measured value (PV) and the set value (SV). Made-in-China.com Key Specifications Input Types:
Remember: When in doubt, start with a factory reset and run auto-tune. Good luck controlling your temperature!
Hy (Hysteresis): Used in ON/OFF mode to prevent rapid switching. xmtd-2201 manual
Common Parameter Codes
| Code | Meaning | Typical Setting | Explanation |
| :--- | :--- | :--- | :--- |
| HC | Heat/Cool | H (Heating) | Set to H for heating control. Set to C for cooling. |
| P | Proportional Band | 2.0 - 30.0 | Lower number = faster reaction but risk of oscillation. |
| I | Integral Time | 100 - 200 | Corrects offset errors. |
| d | Derivative Time | 0 - 50 | Prevents overshoot. |
| AL1 | Alarm 1 | 400 | The temperature at which the alarm triggers. |
| Sn | Sensor Input | 0 (K-type) | Crucial: Must match your sensor. 0 is often K-type thermocouple. Check your specific manual for codes. |
Display shows "EEEE": This usually indicates a sensor error. Check for a broken thermocouple or loose wiring. is a digital temperature controller often used in
Mounting: Insert the controller through the 68x68mm panel cutout and secure it using the provided mounting brackets. Connections: Power: Typically terminals for AC 220V.
Download the official PDF – Search online for:
"XMTD-2201 manual PDF"
Look for results from sites like datasheet.live, manualslib.com, or fotek.com.tw (Fotek makes these). Then print the PDF. Good luck controlling your temperature
| Label | Button Name | Primary Function | | :--- | :--- | :--- | | PV | Upper Display (Red) | Shows actual temperature (Process Value) | | SV | Lower Display (Green) | Shows set temperature (Set Value) | | SET | Set Key | Enter parameter menu / confirm setting | | ◀ or R/S | Shift/Reset | Move cursor during setting / Reset alarm | | ▼ | Down Key | Decrease value | | ▲ | Up Key | Increase value | | AT | Auto-tune LED | Lights when auto-tuning is active | | OUT | Output LED | Lights when heating output is ON | | AL1/AL2 | Alarm LEDs | Light when respective alarms are triggered |